| Load Rating |
| |
Switched Channels |
8 internal; expandable up to 64 by adding external panels and modules |
| |
Per Channel |
16 Amps @ 120 to 277 Volts AC, 50/60 Hz |
| |
Switched Load Types |
Flourescent Ballast, Incandescent, Magnetic Low-Voltage, Electronic Low-Voltage, Neon/Cold Cathode, High-Intensity Discharge, LED, Motor |
| |
Relay Lifetime |
Resistive rating: 100,000 on/off operations, 50A @ 277 VAC; General rating: 50,000 on/off operations, 16A @ 120/277 VAC |
| Power Requirements |
| |
Main Power |
100-277 Volts AC, 50/60 Hz, via channel 1 (LINE 1, NEUT) |
| |
Available Cresnet Power |
15 Watts at 24 Volts DC |
| Connectors (Class 1) |
| |
NEUT |
(2) terminal blocks, paralleled, line input neutral |
| |
LINE 1 - LINE 8 |
(16) terminal blocks; 2 connections per channel, paralleled, allows for easy daisy-chaining; line power inputs |
| |
SW1 - SW8 |
(8) terminal blocks, switch channels outputs |
| Connectors (Class 2) |
| |
CRESNET |
(1) 4-pin 3.5mm terminal block; a maximum of 10 GLS-SIMs may be connected via the Cresnet® terminal block for occupancy sensors and a maximum of 10 GLS-SIMs for photo sensors; up to 20 occupancy sensors may be supported (10 external Cresnet sensors and 10 external, non-system sensors connected to Cresnet via GLS-SIM); up to 20 photo sensors may be supported (10 external, non-system sensors wired directly to a Cresnet occupancy sensor and 10 external, non-system sensors wired to a GLS-SIM using Cresnet) |
| |
OVR |
(1) 2-pin 3.5mm terminal block, comprising (2) inputs for external contact closures to trigger the preset Override state |
| |
CONTACT CLOSURES |
(1) 9-pin 3.5mm terminal block comprising (8) contact closure inputs and (1) GND port |
| |
SENSOR INPUT 1-4 |
(1) 6-pin 3.5mm terminal block comprising (4) sensor inputs for internal, non-system occupancy sensors, (1) +24VDC, and (1) GND port (provides sensors with power) |
| |
SENSOR INPUT 5-8 |
(1) 6-pin 3.5mm terminal block comprising (4) sensor inputs for internal, non-system photo sensors, (1) +24VDC, and (1) GND port (provides sensors with power) |
| |
USB |
(1) USB Type B console port, for communication with Crestron Toolbox™ |
| |
LAN |
(1) 8-wire RJ45 with 2 LED indicators; 10/100BaseT Ethernet port; Green LED indicates link status; Yellow LED indicates Ethernet activity |
| LED Display |
| |
Green LCD dot matrix, 128x64 resolution, adjustable LED backlight |
| Controls & Indicators |
| |
SELECTION BUTTONS |
(2) push-button, adjust menu parameters |
| |
ENTER |
(1) push-button, selects underlined item and stores settings |
| |
HOME |
(1) push-button, returns to the home page |
| |
BACK |
(1) push-button, returns to the previous page |
| |
CANCEL |
(1) push-button, cancels current action without saving |
| |
HELP |
(1) push-button, opens context-sensitive help screen |
| |
Soft Keys |
(4) push-buttons for activation of LCD driven functions |
| |
PWR |
(1) Green LED; solid illumination indicates line power is applied to NEUT and LINE1 |
| |
HW-R |
(1) Recessed miniature push-button for hardware reset (reboots the processor) |
| |
SW-R |
(1) Recessed miniature push-button for software reset (restarts the program) |
| |
OVR |
(1) Red LED and (1) miniature push-button for enabling override mode |
| |
ON/OFF |
(8) Red LEDs and (8) miniature push-buttons for individual manual channel activation |
| Environmental |
| |
Temperature |
32° to 104°F (0° to 40°C) |
| |
Humidity |
10% to 90% RH (non-condensing) |
| Dimensions |
| |
Height |
12.13 in (308 mm) |
| |
Width |
14.13 in (359 mm) |
| |
Depth |
4.06 in (104 mm) |
| Standards & Certifications |
| |
UL Listed Enclosure |
| |