Products

    Pages

        GLX-DIMFLV8

        8 Channel 0-10V Dimmer Module

        • 8 channels of 0-10 Volt dimming control
        • Compatible with lighting and motor loads
        • Supports 100 to 277 Volt applications


        Visit the Crestron® Lighting Fixture Compatibility page to find out which Crestron lighting devices have been tested and are compatible with third party lighting fixtures.

         

        The GLX-DIMFLV8 is a Crestron Green Light® architectural dimming module that features 8 channels of 0-10 Volt dimming control. This module is part of a complete Crestron® engineered GLPD

        Green Light dimming panel.

        For more information on Crestron Green Light commercial lighting products, please contact Crestron Sales Support Services.

         
        Key Features
        • 8 channels of 0-10 Volt dimming control
        • Compatible with lighting and motor loads
        • Support for 100 to 277 Volt applications
        • 16 Amp load rating per channel
        • Arc-less switching
        • Positive air gap at each output
        • Phase-independent channels
        • Cresnet® communications
        • Redundant power capability—module powered via line or Cresnet
        • Local controls for testing and verification
        • Local and remote override capability
        • Non-volatile power failure memory
        • GLE cabinet installation
        • CEC Title 24 2013 Compliant
        1. Line power terminal blocks accept 10-26 AWG wire, torque to 5.31 lb-in (0.6 Nm).
        2. Terminal blocks for 0-10V connections accept 12-28 AWG wire, torque to 4.43 lb-in (0.5 Nm).

        This product may be purchased from an authorized Crestron dealer. To find a dealer, please contact the Crestron sales representative for your area. A list of sales representatives is available online at www.crestron.com/salesreps or by calling 800-237-2041.

         

        The specific patents that cover Crestron products are listed online at: patents.crestron.com.

         

        Crestron, the Crestron Logo, Crestron Green Light, and Cresnet are either trademarks or registered trademarks of Crestron Electronics, Inc. in the United States and/or other countries. Other trademarks, registered trademarks, and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Crestron disclaims any proprietary interest in the marks and names of others. Crestron is not responsible for errors in typography or photography. Specifications are subject to change without notice. ©2015 Crestron Electronics, Inc.

         
        Load Ratings
          Dimmer Channels 8
          Per Channel 16 Amps @ 100 to 277 Volts AC, 50/60 Hz;
        0.5 HP @ 120 Volts, 1 HP @ 230 Volts, 1 HP @ 277 Volts
          Dim Load Types 0-10 Volt fluorescent ballast or LED driver (4-wire);
        60 mA max current sink
          Switch Load Types Incandescent, magnetic low-voltage, electronic low-voltage, neon/cold cathode, fluorescent ballast, high-intensity discharge, motor, LED
          Relay Lifetime 1,000,000 on/off operations at full electronic ballast load
        Power Requirements
          Primary 100-277 Volts AC, 50/60Hz, supplied via channel 1 (L1, N)
          Secondary (optional) 5 Watts @ 24 Volts DC, supplied via Cresnet®
        Connectors
          NET (2) 5-pin headers, connects via included interconnect cable to adjacent module or internal connecting block
          N (1) terminal block, line input neutral
          L1-L8 (8) Terminal blocks,[1] line power inputs
          SW1-SW8 (8) Terminal blocks, switch channel outputs
          0-10V DIM (COMMON) (1) 8-position terminal block,[2] dim channel common
          0-10V DIM (+) (1)-8 position terminal block,[2] dim channel output, galvanically isolated;
        May be wired as Class 1 or Class 2
        Controls & Indicators
          NET ID (2) 7-segment green LED digits and (2) miniature pushbuttons, sets Cresnet ID
          SETUP (1) Red LED and (1) recessed miniature pushbutton, enables setup mode and touch-settable ID
          OVR (1) Red LED and (1) miniature pushbutton, enables override mode and saves override presets
          PWR (1) Green LED, indicates power status;
        Solid illumination indicates line power is applied to N and L1;
        Flashing indicates Cresnet power is supplied in absence of line power
          NET (1) Yellow LED, indicates communication with control processor
          RESET (1) Recessed miniature pushbutton, resets internal processor
          Channel Section
          ON/DIM (2) Red LEDs per each channel, "ON" indicates channel is at a non-zero level, "DIM" indicates channel is at a non-zero level below 100%
          UP/DN (16) Miniature pushbuttons, manually activates individual channels for dimming
          DIM/NON-DIM (8) Recessed miniature switches, sets channel mode;
        When set to "NON-DIM" module will ignore dim commands
        Enclosure
          Surface mount module, mounts in a GLE enclosure
        Environmental
          Temperature 32° to 104° F (0° to 40° C)
          Humidity 10% to 90% RH (non-condensing)
          Heat Dissipation 116 BTU/Hr
        Dimensions
          Height 14.5 in (368 mm)
          Width 6 in (152 mm)
          Depth 3.04 in (77 mm)
        Electrical Regulatory Certifications
          UL508, Section 41 (Endurance Test) and Section 61C (Electronic Ballasts)
          UL924, Emergency Power Equipment
          IEC60669-2-1, Section 19.102 (Contact mechanisms incorporated in electronic switches, intended for fluorescent lamp circuits or other capacitive loads)
          SCCR Rating - 65kA
          CE
          CEC Title 24 2013 Compliant
        1. Line power terminal blocks accept 10-26 AWG wire, torque to 5.31 lb-in (0.6 Nm).
        2. Terminal blocks for 0-10V connections accept 12-28 AWG wire, torque to 4.43 lb-in (0.5 Nm).

        This product may be purchased from an authorized Crestron dealer. To find a dealer, please contact the Crestron sales representative for your area. A list of sales representatives is available online at www.crestron.com/salesreps or by calling 800-237-2041.

         

        The specific patents that cover Crestron products are listed online at: patents.crestron.com.

         

        Crestron, the Crestron Logo, Crestron Green Light, and Cresnet are either trademarks or registered trademarks of Crestron Electronics, Inc. in the United States and/or other countries. Other trademarks, registered trademarks, and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Crestron disclaims any proprietary interest in the marks and names of others. Crestron is not responsible for errors in typography or photography. Specifications are subject to change without notice. ©2015 Crestron Electronics, Inc.