ST-IO

Cresnet Module with 8 Relays and 4 Analog/Digital Inputs.

Discontinued

This product has been discontinued. Please contact Crestron True Blue Support at 1-888-CRESTRON for a replacement solution or more information.

An expansion module for Crestron control systems to provide multiple low-voltage relays and digital/analog input sensing ports.

The ST-IO is a Cresnet® expansion module that provides eight low-voltage relay outputs and four digital/analog input ports. Typical applications include control of lighting, screens, drapes, and more. In "closure" mode, each input port will sense a contact closure signal from a door switch, motion sensor, etc., and can also accept analog 0-24 Volt DC signals when in "voltage" mode. The ST-IO may be used to provide a low-voltage control interface at a remote location, or may be rack mounted in the central equipment cabinet to expand the number of control system ports (ST-RMK rack mount kit sold separately). Communication with the control system is via a single Cresnet connection.

 

Crestron and Cresnet are trademarks of Crestron Electronics, Inc. Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Crestron disclaims proprietary interest in the marks and names of others.

 
Connectors
  RELAY OUTPUT 1 – 8 (1) 16-pin 5mm detachable terminal block comprising (8) normally open, isolated relays;
Rated 1 Amp, 30 Volts AC/DC maximum; 100µA, 100mV minimum
  DIGITAL IN 1 – 4 (1) 5-pin 5mm detachable terminal block comprising (4) digital or analog input ports (referenced to GND);
Digital Input (closure mode): Input threshold 2 Volts DC (±0.5VDC); input impedance 1k ohms to +5VDC; 5 Volt, 1k ohms pull-up resistor and protection diode per pin;
Analog Input (voltage mode): Input threshold 2 Volts DC (±0.5VDC); voltage range 0-24 Volts DC; input impedance 44k ohms
  NET (2) 6-pin RJ11 female, Cresnet slave ports, paralleled;
Connect to Cresnet control network
  12VDC (1) 2.5mm barrel DC power jack;
12 Volt DC power input (PW-1205 power pack included)
Indicators
  PWR (1) green LED, indicates power supplied from Cresnet network or local power pack
  NET (1) amber LED, indicates communication with Cresnet system
  INPUT 1 – 4 (4) red LEDs, indicate a high signal at each corresponding digital input port
  RELAY 1 – 8 (4) red LEDs, indicate a closure at each corresponding relay output port
Power Requirements
  Power Pack 0.5 Amp @ 12 Volts DC;
120 Volts AC, 60 Hz power pack, model PW-1205, included
  Cresnet Power Usage 6 Watts (0.25 Amp @ 24 Volts DC) with no power pack connected
Environmental
  Temperature 41° to 113°F (5° to 45°C)
  Humidity 10% to 90% RH (non-condensing)
Enclosure
  Chassis Metal, black finish
  Faceplate Extruded aluminum, black finish with polycarbonate label overlay
  Mounting Freestanding or 1U 1/2-width 19-inch rack-mountable (adhesive feet included, ST-RMK rack kit sold separately)
Dimensions
  Height 1.80 in (46 mm);
1.70 in (44 mm) without feet
  Width 7.07 in (180 mm)
  Depth 6.32 in (161 mm)
Weight
  1.96 lb (0.89 kg)
INTERNATIONAL VERSION (230 VAC)
  STI-IO
  All the features and specifications of the ST-IO except:
  Power Requirements
  Power Pack 0.5 Amp @ 12 Volts DC;
230 Volts AC, 50 Hz power pack, model PWI-1215, included
  Cresnet Power Usage 6 Watts (0.25 Amp @ 24 Volts DC) with no power pack connected