Cresnet Module with 8 Relays and 4 Analog/Digital Inputs.
This product has been discontinued. Please contact Crestron True Blue Support at 1-888-CRESTRON for a replacement solution or more information.
An expansion module for Crestron control systems to provide multiple low-voltage relays and digital/analog input sensing ports.
The ST-IO is a Cresnet® expansion module that provides eight low-voltage relay outputs and four digital/analog input ports. Typical applications include control of lighting, screens, drapes, and more. In "closure" mode, each input port will sense a contact closure signal from a door switch, motion sensor, etc., and can also accept analog 0-24 Volt DC signals when in "voltage" mode. The ST-IO may be used to provide a low-voltage control interface at a remote location, or may be rack mounted in the central equipment cabinet to expand the number of control system ports (ST-RMK rack mount kit sold separately). Communication with the control system is via a single Cresnet connection.
| Connectors |
| |
RELAY OUTPUT 1 – 8 |
(1) 16-pin 5mm detachable terminal block comprising (8) normally open, isolated relays;
Rated 1 Amp, 30 Volts AC/DC maximum; 100µA, 100mV minimum |
| |
DIGITAL IN 1 – 4 |
(1) 5-pin 5mm detachable terminal block comprising (4) digital or analog input ports (referenced to GND);
Digital Input (closure mode): Input threshold 2 Volts DC (±0.5VDC); input impedance 1k ohms to +5VDC; 5 Volt, 1k ohms pull-up resistor and protection diode per pin;
Analog Input (voltage mode): Input threshold 2 Volts DC (±0.5VDC); voltage range 0-24 Volts DC; input impedance 44k ohms |
| |
NET |
(2) 6-pin RJ11 female, Cresnet slave ports, paralleled;
Connect to Cresnet control network |
| |
12VDC |
(1) 2.5mm barrel DC power jack;
12 Volt DC power input (PW-1205 power pack included) |
| Indicators |
| |
PWR |
(1) green LED, indicates power supplied from Cresnet network or local power pack |
| |
NET |
(1) amber LED, indicates communication with Cresnet system |
| |
INPUT 1 – 4 |
(4) red LEDs, indicate a high signal at each corresponding digital input port |
| |
RELAY 1 – 8 |
(4) red LEDs, indicate a closure at each corresponding relay output port |
| Power Requirements |
| |
Power Pack |
0.5 Amp @ 12 Volts DC;
120 Volts AC, 60 Hz power pack, model PW-1205, included |
| |
Cresnet Power Usage |
6 Watts (0.25 Amp @ 24 Volts DC) with no power pack connected |
| Environmental |
| |
Temperature |
41° to 113°F (5° to 45°C) |
| |
Humidity |
10% to 90% RH (non-condensing) |
| Enclosure |
| |
Chassis |
Metal, black finish |
| |
Faceplate |
Extruded aluminum, black finish with polycarbonate label overlay |
| |
Mounting |
Freestanding or 1U 1/2-width 19-inch rack-mountable (adhesive feet included, ST-RMK rack kit sold separately) |
| Dimensions |
| |
Height |
1.80 in (46 mm);
1.70 in (44 mm) without feet |
| |
Width |
7.07 in (180 mm) |
| |
Depth |
6.32 in (161 mm) |
| Weight |
| |
1.96 lb (0.89 kg) |
| INTERNATIONAL VERSION (230 VAC) |
| |
STI-IO |
| |
All the features and specifications of the ST-IO except: |
| |
Power Requirements |
| |
Power Pack |
0.5 Amp @ 12 Volts DC;
230 Volts AC, 50 Hz power pack, model PWI-1215, included |
| |
Cresnet Power Usage |
6 Watts (0.25 Amp @ 24 Volts DC) with no power pack connected |