Device Support |
|
Occupancy/Vacancy Sensors |
Supports one or more 24 VDC powered motion detection type sensors wired in parallel;
Requires a maintained DC high logic signal >8 VDC, 24 VDC maximum when detecting occupancy (motion);
Operates in either occupancy or vacancy mode depending on connection used (do not connect both);
Compatible Crestron models: GLS-ODT-C-NS, GLS-OIR-C-NS, GLA-IR-QUATTRO-HD-COM1-24, GLA-IR-QUATTRO-HD-COM2-24, GLA-US-HALLWAY-COM1-24 |
|
Daylight Sensors |
Supports a single 24 VDC powered open-loop photosensor (photocell) type sensor;
Requires a 0-10 VDC analog control signal to indicate the natural daylight level;
Compatible Crestron models: GLS-LOL |
|
Note: Supplies a maximum or 250 mA @ 24 VDC to power all connected sensors. An external power supply may be used to power greater loads. Only one daylight sensor is permitted per room (do not connect a wired daylight sensor to this module if the room is already equipped with a Zūm wireless daylight sensor). |
|
Accessory Modules |
Supports one ZUMMESH-NETBRIDGE or one ZUMMESH-CCO module |
Wireless Communications |
|
RF Transceiver |
Zūm Mesh & Zūm Net 2-way RF, 2.4 GHz ISM Channels 15, 20, 25, or 26 (channel auto-selected), IEEE 802.15.4 compliant, AES-128 encryption |
|
Zūm Mesh Range |
50 ft (15 m) to nearest Zūm Mesh peer-to-peer mesh network device(s), subject to site-specific conditions and individual device capabilities [2] |
|
Zūm Net Range |
50 ft (15 m) to a Zūm Net wireless gateway or nearest Zūm Net mesh network device(s), requires the Zūm Network Bridge (model ZUMMESH-NETBRIDGE [1]), range between floors or ceilings is limited to one level, subject to site-specific conditions and individual device capabilities [2] |
|
Note: A maximum of 32 Zūm Mesh wireless devices is permitted per room. Only one Network Bridge is permitted per room. Only one daylight sensor (wired or wireless) is permitted per room. |
Controls & Indicators |
|
SETUP |
(1) Pushbutton and (1) red LED, used for sensor calibration, test mode, room setup, and factory reset |
|
TEST |
(1) Pushbutton and (1) green LED, used for installation test, room setup, and factory reset |
Connections |
|
Hot |
(1) Class 1 flying lead, black, line power input |
|
Neutral |
(1) Class 1 flying lead, white, neutral |
|
Ground |
(1) Class 1 flying lead, green, ground |
|
24 |
(1) Stab terminal, 24 Volt DC sensor power output |
|
O |
(1) Stab terminal, occupancy sensor input, detection threshold >8 Volts DC, 24 Volts DC maximum |
|
V |
(1) Stab terminal, vacancy sensor input, detection threshold >8 Volts DC, 24 Volts DC maximum |
|
D |
(1) Stab terminal, daylight sensor input, sensing range 0-10 Volts DC, 24 Volts DC maximum |
|
G |
(1) Stab terminal, ground/common connection for sensors |
|
Expansion Port |
Accessory port for optional Zūm Network Bridge or Zūm Contact Closure Output (model ZUMMESH-NETBRIDGE or ZUMMESH-CCO [1]) |
|
Note: Stab terminals support 22-16 AWG (0.5-1.5 mm²) wire size; maximum wire distances are 250 ft (76 m) for occupancy or vacancy sensors and 50 ft (15 m) for daylight sensors |
Power |
|
Line Power |
100-277 Volts AC, 50/60 Hz |
|
Idle Power Consumption |
<1 Watt |
|
Output Power |
250 mA @ 24 Volts DC |
Environmental |
|
Temperature |
32° to 104° F (0° to 40° C) |
|
Humidity |
10% to 90% RH (non-condensing) |
Construction |
|
Housing |
Plastic, white, UL 94 5VA flame rated |
|
Mounting |
Mounts to the side of a 4-inch square junction box via a 1/2 inch conduit knockout, meets the requirements of UL 2043 for installation in an environmental air-handling (plenum) space |
Dimensions |
|
Height |
3.25 in (83 mm) |
|
Width |
4.17 in (106 mm) |
|
Depth |
1.32 in (34 mm) |
|
Note: Projects 3.66 inches (93 mm) from the junction box when installed. |
Weight |
|
7 oz (199 g) |
Compliance |
|
UL Listed for US & Canada, IC, FCC Part 15 Class B digital device, UL 2043, UL 94 5VA |