        DIN Rail Universal Dimmer, 1 feed, 4 channels

         

        • 4 channels of forward or reverse phase dimming
        • Auto load detection
        • 120 to 240 Volt 50/60 Hz operation

        Visit the Crestron® Lighting Fixture Compatibility page to find out which Crestron lighting devices have been tested and are compatible with third party lighting fixtures.

         

        The DIN-1DIMU4 is a 4-channel universal lighting control module designed to support dimming of both forward and reverse phase type loads. A single model supports both 120 and 220-240 Volt electronic and magnetic low-voltage, incandescent, neon/cold cathode, 2-wire dimmable fluorescent, and non-dimmable lighting loads up to 5 Amps per channel, 10 Amps total.

        Auto Load Detection

        Each channel of the DIN-1DIMU4 is capable of auto-detecting the dimmable load type connected to it and selecting the appropriate operating mode to control that load. Reverse phase (trailing edge) mode supports incandescent and electronic low-voltage load types, while forward phase (leading edge) mode handles magnetic low-voltage, neon, and other inductive load types. A non-dim mode is also selectable for switching of non-dimmable lighting fixtures. Any channel may be set for any mode, allowing one dimmer module to handle any combination of lighting types on four separately controlled circuits.

        Phase-Synchronous Detection Circuitry

        Crestron's proprietary zero cross filter technology provides superior immunity to noise on the power line, reducing lamp flicker and compensating for fluctuations in line voltage and frequency.

        Short Circuit Protection

        Built-in OCP (over current protection) prevents failure of the DIN-1DIMU4 caused by excessive loading or improper wiring of the outputs.

        Master Air-Gap Relay

        When all four channels are turned fully off, the internal master relay automatically opens providing air-gap isolation to allow safe servicing and changing of light bulbs on all four controlled circuits.

        Override Input

        An override input is provided to allow an external contact closure to momentarily override the control system program and set each channel output to its override preset level. Levels can be adjusted and saved locally from the front panel or remotely via software.

        DIN Rail Installation

        The DIN-1DIMU4 is designed to snap onto a standard DIN rail for installation in a wall mount enclosure. Wiring connections are made using screw terminals positioned along the bottom, clearly accessible from the front for easy installation and servicing. All setup controls and indicators are positioned on the center front panel. When installed in an enclosure utilizing 45 mm cutouts, the DIN-1DIMU4's front panel stays accessible while the connections are concealed.

        Cresnet®

        The DIN-1DIMU4 communicates with a DIN-AP2 2-Series Automation Processor, or other Crestron 2-Series control system, via the Cresnet control network. A pair of Cresnet ports is provided on the DIN-1DIMU4 allowing for easy daisy-chaining of several DIN Rail Series automation control modules.

         
        Key Features
        • 4 channels of forward or reverse phase dimming
        • Auto load detection
        • 120 to 240 Volt 50/60 Hz operation
        • Selectable non-dim mode
        • Extreme stability in noisy environments
        • Short circuit and overload protection
        • Master air-gap relay
        • Override input
        • Cresnet® communications
        • Setup via front panel or software
        • Programmable functionality via DIN-AP2
        • 12M wide DIN rail mounting
        • CEC Title 24 2013 Compliant
        1. Captive screw terminals accept up to 12 AWG (2.5 mm²) wires per terminal.
        2. Unit dissipates significant heat when fully loaded and should be mounted in an enclosure that is sufficiently ventilated to maintain an ambient temperature not exceeding 104°F (40°C). Maintain 4 inches (10 cm) minimum spacing above and below for proper ventilation and heat dissipation, 6 inches (15 cm) spacing recommended.

        This product may be purchased from an authorized Crestron dealer. To find a dealer, please contact the Crestron sales representative for your area. A list of sales representatives is available online at www.crestron.com/salesreps or by calling 800-237-2041.

         

        The specific patents that cover Crestron products are listed online at: patents.crestron.com.

         

        Crestron, the Crestron logo, and Cresnet are either trademarks or registered trademarks of Crestron Electronics, Inc. in the United States and/or other countries. Other trademarks, registered trademarks, and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Crestron disclaims any proprietary interest in the marks and names of others. Crestron is not responsible for errors in typography or photography. Specifications are subject to change without notice. ©2015 Crestron Electronics, Inc.

         
        Pyng
        Load Ratings
          Dimmer Channels 4
          Maximum Per Channel 5 Amps @ 120 to 240 Volts AC, 50/60 Hz;
        600 Watts @ 120 Volts AC;
        1150 Watts @ 230 Volts AC;
        1200 Watts @ 240 Volts AC
          Module Total 10 Amps @ 120 to 240 Volts AC, 50/60 Hz;
        1200 Watts @ 120 Volts AC;
        2300 Watts @ 230 Volts AC;
        2400 Watts @ 240 Volts AC
          Load Types Forward Phase (leading edge) or Reverse Phase (trailing edge) Electronic Low Voltage, Incandescent, Neon/Cold Cathode, Magnetic Low Voltage, Dimmable 2 Wire Fluorescent, & Non-Dim Lighting
          Minimum Load 15 Watts/channel for Incandescent loads;
        50 Watts/channel for Magnetic Low Voltage loads with Halogen or LED Lamps;
        50 Watts for AC Dimmable LED loads operated in Auto/Forward-Phase Mode;
        15 Watts for AC Dimmable LED loads operated in Reverse-Phase Mode
        Input Voltage
          Line Power 120 to 240 Volts AC, 50/60 Hz
        Connections
          NET (2) 4-pin 3.5mm detachable terminal blocks, paralleled;
        Cresnet® slave port
          OVERRIDE (2) 2-pin 3.5mm detachable terminal blocks, paralleled;
        Sensing input for external low-voltage contact closure;
        Activates override mode when a closure is present;
        Minimum Closure Rating: 10mA (per module) at 24 Volts
          LIVE (2) Captive screw terminals,[1] brown;
        Line power input
          NEUTRAL (5) Captive screw terminals,[1] blue
          DIMMED LIVE 1 – 4 (4) Captive screw terminals,[1] red;
        Dimmer channel outputs 1 - 4
          Ground (5) Captive screw terminals,[1] green
        Controls & Indicators
          NET ID (2) 7-Segment green LED digits and (2) miniature pushbuttons for setting Cresnet ID; digits also display output levels and protection/error codes
          SETUP (1) Red LED and (1) recessed miniature pushbutton for enabling setup mode and touch-settable ID
          OVR (1) Red LED and (1) miniature pushbutton for enabling override mode and saving override presets
          PWR (1) Green LED, normally indicates AC line power is connected to either LIVE terminal, blinks when only powered by Cresnet
          NET (1) Yellow LED, indicates communication with the control processor
          RESET (1) Recessed miniature pushbutton, resets internal processor
          FWD 1 – 4 (4) Red LEDs, illuminate when a corresponding channel is operating in forward-phase mode
          REV 1 – 4 (4) Red LEDs, illuminate when a corresponding channel is operating in reverse-phase mode
          AUTO 1 – 4 (4) Red LEDs, illuminate when a corresponding channel is set to auto-detect the load type
          NON-DIM 1 – 4 (4) Red LEDs, illuminate when a corresponding channel is operating in non-dim mode
          Channel Mode Select 1 – 4 (4) Recessed miniature pushbuttons, used to select each channel’s operating mode
          LOADS 1 – 4 (4) Red LEDs and (4) miniature pushbuttons for status indication and local control of each channel
        Enclosure
          Aluminum with polycarbonate label overlay, 35mm DIN EN 60715 rail mount, DIN 43880 form factor for enclosures with 45mm front panel cutout, occupies 12 DIN module spaces (216mm)[2]
        Power Requirements
          Cresnet Power Usage 0.6 Watts (0.03 Amps @ 24 Volts DC) when line power is not available
        Environmental
          Temperature 32° to 104°F (0° to 40°C)
          Humidity 10% to 90% RH (non-condensing)
          Heat Dissipation 60 BTU/hr @240 Volts with 2 channels at 5 Amps;
        50 BTU/hr @ 120 Volts with 2 channels at 5 Amps
        Dimensions
          Height 3.71 in (95 mm)
          Width 8.49 in (216 mm)
          Depth 2.35 in (60 mm)
        Weight
          2.1 lbs. (0.96 kg)
        Standards & Certifications
          CEC Title 24 2013 Compliant
        1. Captive screw terminals accept up to 12 AWG (2.5 mm²) wires per terminal.
        2. Unit dissipates significant heat when fully loaded and should be mounted in an enclosure that is sufficiently ventilated to maintain an ambient temperature not exceeding 104°F (40°C). Maintain 4 inches (10 cm) minimum spacing above and below for proper ventilation and heat dissipation, 6 inches (15 cm) spacing recommended.

        This product may be purchased from an authorized Crestron dealer. To find a dealer, please contact the Crestron sales representative for your area. A list of sales representatives is available online at www.crestron.com/salesreps or by calling 800-237-2041.

         

        The specific patents that cover Crestron products are listed online at: patents.crestron.com.

         

        Crestron, the Crestron logo, and Cresnet are either trademarks or registered trademarks of Crestron Electronics, Inc. in the United States and/or other countries. Other trademarks, registered trademarks, and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Crestron disclaims any proprietary interest in the marks and names of others. Crestron is not responsible for errors in typography or photography. Specifications are subject to change without notice. ©2015 Crestron Electronics, Inc.